Regulation guide

Schedule 2, paragraphs 11, 15 and 28

24 Nov 2026

13

Showers, Baths & Bidets

PropertyValue
Type AUK2 tap gap20 mm, 25 mm or 70 mm, depending on tap connection size
Type AUK3 tap gapMinimum 20 mm or twice the inlet-pipe internal diameter, whichever is greater
Domestic bath/shower riskTypically Fluid Category 3, subject to intended use
High-risk showers and bidetsFluid Category 5
Recommended shower TMV settingMaximum 41°C (healthcare guidance)
Recommended bidet TMV settingMaximum 38°C (healthcare guidance)
Hot water storage temperatureAt least 60°C (HSE guidance)

Bathrooms contain a range of water fittings that can present backflow risks. The protection required depends on the fitting, its intended use and the environment in which it is installed.

Many modern buildings use mains-pressure or boosted hot and cold water supplies. These systems can offer improved flow rates and simpler distribution arrangements compared with traditional gravity-fed systems.

However, higher-pressure installations require careful consideration of backflow protection, particularly where shower hoses or other outlets can become submerged.

Schedule 2, paragraph 15 of the Water Supply (Water Fittings) Regulations 1999 requires adequate protection against backflow from appliances, fittings and processes.

Public and healthcare bathrooms must also address water hygiene and the risk of scalding.

Water Pressure and Bathroom Fittings

Older buildings often have mains-pressure cold water and gravity-fed hot water supplied from a storage cistern.

This can result in unbalanced hot and cold pressures at mixer taps and showers.

Some modern bathroom fittings require relatively high supply pressures to operate effectively. Thermostatic Mixing Valves (TMVs) also have specified operating pressure ranges and differential pressure requirements.

Where supply pressures are significantly different, the performance of the mixer can be affected.

Designers should check the pressure and flow requirements of the selected fittings rather than assuming they will operate satisfactorily on an existing gravity-fed system.

Baths — Domestic Installations

A domestic bath with separate hot and cold taps can provide backflow protection through the gap between the tap outlets and the bath’s spill-over level.

For a typical domestic installation assessed as Fluid Category 3, this is known as a Type AUK2 tap gap.

The required clearance depends on the tap connection size:

Tap connection sizeMinimum Type AUK2 tap gap
Up to and including ½″20 mm
Exceeding ½″ but not exceeding ¾″25 mm
Exceeding ¾″70 mm

The gap is measured vertically from the lowest point of the tap outlet to the spill-over level of the bath.

Where the required gap is maintained, additional backflow protection for the risk addressed by that gap is not normally necessary.

However, where a tap outlet can become submerged or the required gap cannot be maintained, an alternative form of backflow protection is required.

Baths in Higher-Risk Environments

Baths in healthcare premises, nursing homes and other higher-risk environments can be classified as Fluid Category 5.

A Type AUK2 tap gap is not sufficient for this risk.

Where a tap gap is used to provide Fluid Category 5 back-siphonage protection, it must meet the requirements of Type AUK3.

The minimum clearance is:

  • 20 mm; or
  • Twice the internal diameter of the supply pipe.

Whichever is greater.

For example, a tap connection with a 19 mm internal diameter requires a minimum gap of 38 mm.

Where a suitable tap gap cannot be maintained, an appropriate alternative Fluid Category 5 protection arrangement is required.

The local water undertaker determines the level of protection required for the installation.

Shower Hoses — Domestic Installations

A shower with a fixed outlet that maintains the required separation from potential contamination does not generally require additional protection against back-siphonage through that outlet.

Flexible shower hoses require particular attention because the handset can be moved and potentially submerged.

Fluid Category 3 Protection

In a typical domestic installation, a shower handset capable of reaching bath or shower-tray water can present a Fluid Category 3 risk.

Where the required Type AUK2 tap gap cannot be maintained, suitable protection can be provided through:

  • A Double Check Valve (Type ED or EC).
  • An approved diverter with automatic return (Type HC).

A Type HC device automatically returns the flow to an outlet open to atmosphere when the supply pressure falls, providing Fluid Category 3 back-siphonage protection.

Arrow Valves offers the ED235 Double Check Valve, designed for suitable shower-hose connections.

This is also available with an optional flow-limiting arrangement.

Arrow’s Equi-Flow (AFLE) provides flow limiting without Double Check Valve protection.

Shower Hoses That Can Reach a WC or Bidet

An important distinction applies where a shower hose can reach a WC pan or bidet.

This is considered a Fluid Category 5 risk, including in domestic premises.

Unless the hose is permanently restrained or shortened to maintain a suitable Type AUK3 tap gap, the shower must be supplied through appropriate Fluid Category 5 backflow protection.

A Type AB break tank arrangement is one method of providing this protection.

A Double Check Valve or Type HC device alone is not sufficient for Fluid Category 5.

Double Check Valves

Double Check Valves provide backflow protection against Fluid Category 3 risks.

They are commonly used where a suitable tap gap or Type HC diverter cannot be provided.

However, Double Check Valves create resistance to flow, which must be considered during design.

The pressure loss increases as the flow rate rises.

For example, the original Arrow tutorial identifies that some 15 mm Double Check Valves can create approximately 0.5 bar head loss at a pipe velocity of 3 m/s.

Where several Double Check Valves are installed in series, the combined pressure loss can significantly reduce the available flow, particularly at higher floors or on low-pressure systems.

Arrow Valves’ ED132 Double Check Valve is designed for low head loss, with the original technical data identifying approximately 0.1 bar at a pipe velocity of 3 m/s.

Verifiable and Non-Verifiable Double Check Valves

Double Check Valves can be classified as:

  • Type EC: Verifiable Double Check Valve.
  • Type ED: Non-verifiable Double Check Valve.

Both provide Fluid Category 3 protection when correctly selected and installed.

A Type EC incorporates test points, whereas a Type ED does not.

The appropriate device should be selected according to the installation and any specific requirements of the water undertaker.

Mixer Showers and Unbalanced Pressures

Mixer showers combine hot and cold water supplies.

Where the supplies operate at different pressures, water can pass between the hot and cold connections under certain fault conditions.

Single Check Valves (Type EB) can be used to prevent crossflow between the supplies.

These are sometimes incorporated within the mixer valve itself.

Arrow Valves’ EB235 is a Single Check Valve used for suitable Fluid Category 2 applications.

A Single Check Valve does not replace the Fluid Category 3 or 5 protection required where a shower handset can come into contact with contaminated water.

Baths and Showers — Healthcare Premises

Baths and showers in hospitals, nursing homes and other healthcare facilities can present Fluid Category 5 contamination risks.

This is particularly relevant where flexible shower hoses can become submerged in bathwater or reach a WC or bidet.

Both the hot and cold supplies must be protected against the assessed contamination risk.

Gravity-Fed Systems

The original Arrow tutorial describes a suitable storage cistern incorporating an air gap and dedicated distributing pipework.

The complete arrangement must provide the necessary protection for the assessed risk.

Sharing distributing pipework between several outlets requires careful consideration of possible cross-contamination and the conditions accepted by the local water undertaker.

Mains-Pressure and Boosted Systems

For mains-pressure and boosted systems, a break tank incorporating a Type AB air gap provides Fluid Category 5 protection.

A booster pump can restore the pressure required for baths and showers.

Arrow Valves’ Boost-A-Break® (BTAB) combines a Type AB break tank with a booster pump.

It can supply protected water to suitable bathroom installations, including arrangements serving several baths.

A Type DC pipe interrupter is not generally suitable for a shower handset because the restriction created by the shower head can interfere with the operation of the atmospheric vent arrangement.

Protecting Hot and Cold Supplies

Providing suitable protection on the cold-water supply alone does not automatically protect the downstream hot-water system against contamination from a shower or bath outlet.

Hot water used for personal washing must remain suitable for that purpose.

The design must also prevent contamination between different outlets connected to the same distribution system.

Where several baths or showers are proposed to share a protected supply, the arrangements should be assessed and agreed with the local water undertaker.

Care Showers

Healthcare showers must address both contamination and scalding risks.

The original Arrow tutorial describes the Care Shower CSABATLF, combining a thermostatic electric shower with a booster pump package and Fluid Category 5 protection through a Type AB air gap.

This arrangement is intended to prevent contaminated water from entering the wholesome supply if the shower hose becomes submerged.

The selected shower must also provide appropriate temperature control for its intended users.

Bidets and Ablution Hoses

Bidets and hoses used for personal cleansing require careful consideration because of the potential for contact with contaminated water.

The Water Regulations distinguish between different bidet arrangements.

Over-Rim Bidets

An over-rim bidet has a tap outlet above the spill-over level.

In a typical domestic installation where the risk is assessed as Fluid Category 3, a suitable Type AUK2 tap gap can provide protection against back-siphonage.

In higher-risk environments, such as healthcare premises, the installation can require Fluid Category 5 protection.

Where a tap gap is used, the higher-risk arrangement requires a Type AUK3 gap.

The classification depends on the design, intended use and assessment of risk.

Ascending Spray Bidets and Ablution Hoses

Bidets incorporating an ascending spray, and bidet or ablution hoses that can become submerged, present Fluid Category 5 risks.

Both cold and hot water supplies require suitable Fluid Category 5 backflow protection.

For mains-pressure or boosted systems, a break tank incorporating a Type AB air gap provides an appropriate protection arrangement.

The water provided for personal cleansing must also be suitable for that purpose.

Hot-Water Arrangements

Where a bidet or ablution hose requires warm water, the installation must address both backflow protection and safe water temperatures.

A suitable arrangement can incorporate:

  • A dedicated break tank with a Type AB air gap.
  • A booster pump.
  • Water-heating equipment.
  • A Thermostatic Mixing Valve (TMV).

Hot water must be stored and distributed at temperatures appropriate for controlling microbial growth, with the final outlet temperature controlled to reduce scalding risk.

For stored hot-water systems, HSE guidance recommends storage at a minimum of 60°C.

A TMV can then blend the hot and cold water close to the outlet to provide a safe temperature.

Arrow Valves Ablution Systems

BTHW Ablution Unit

Arrow Valves’ BTHW Ablution Unit is designed to provide point-of-use Fluid Category 5 backflow protection for bidets and ablution hoses.

The unit incorporates:

  • A break tank with Type AB air gap.
  • A booster pump.
  • Water heater.
  • Thermostatic temperature control.

The original tutorial specifies a heater thermostat setting of 62°C and an integrated TMV3 mixing valve.

The unit is normally installed within a cabinet or accessible service space and provides warm water to an adjacent bidet or ablution hose.

BTMIDI-HS Hot Water Midi-Break

The original tutorial also describes the BTMIDI-HS.

This arrangement uses existing hot and cold water supplies and incorporates point-of-use Fluid Category 5 backflow protection.

The unit purges the break tank contents after use, reducing the potential for warm water to remain stored between operations.

This provides an alternative to a unit incorporating its own water heater, subject to the installation requirements.

Handbasins

Cold water intended for drinking must be wholesome and protected against contamination.

Where non-drinking water is supplied to an outlet, suitable identification and labelling should be provided to prevent accidental use.

Water Regs UK recommends that taps in non-household premises are labelled where necessary to distinguish drinking water from non-drinking water supplies.

Water Conservation

Where handbasins are provided without plugs, Schedule 2, paragraph 28 establishes the relevant requirements and exemptions.

Self-closing taps can reduce unnecessary water consumption.

Automatic Flow Limiting Valves can also be used to control flow rates, reduce splashing and improve consistency across multiple outlets.

Arrow Valves’ AFL Servicing Valves combine isolation with optional flow limiting and filtration.

Controlling individual outlet flow rates can also assist with calculating the total demand on the pipework and water supply plant.

Thermostatic Mixing Valves (TMVs)

TMVs blend hot and cold water to maintain a controlled outlet temperature.

They are particularly important where users are at increased risk of scalding, including healthcare facilities, care homes, schools and other relevant public settings.

The type of valve and appropriate outlet temperature depend on the application and the risk assessment.

Point-of-Use and Group Mixing

TMVs should generally be installed as close as practical to the outlet they serve.

A single TMV can sometimes supply several nearby outlets, such as a group of handbasins.

However, group mixing can result in longer lengths of mixed-temperature pipework, increasing the potential for stagnation and microbial growth.

Group mixing is therefore less suitable for certain high-risk applications.

The relevant healthcare guidance and the local water safety risk assessment should inform the arrangement.

Recommended TMV Temperatures

NHS healthcare guidance provides different recommended maximum set temperatures depending on the application.

The values below are based on the table in the original Arrow tutorial and the relevant healthcare guidance.

ApplicationMaximum recommended set temperature
Wash hand basin41°C*
Shower41°C
Bidet38°C
Bath — unassisted44°C
Bath — assisted46°C, exceptional circumstances only

The 41°C washbasin figure is taken from the original Arrow TMV selection table. Current healthcare guidance requires a site-specific scalding risk assessment for washbasins rather than prescribing one setting for every installation.

Bath filling at temperatures above 44°C should only be considered in exceptional circumstances where an adequate bathing temperature cannot otherwise be achieved.

Appropriate supervision, safety procedures and checks must be in place before a vulnerable person enters the bath.

These are healthcare application recommendations, not a universal maximum temperature requirement for every outlet in every public building.

Selecting the Correct TMV

TMVs should be selected according to their certified applications and operating pressures.

For example, the original Arrow tutorial identifies the following TMV3 designations and suggested AFL cartridge flow rates:

ApplicationHigh-pressure designationLow-pressure designationSuggested AFL flow
Wash hand basinHP-WLP-W2 × 0.07 L/s
ShowerHP-SLP-S2 × 0.13 L/s
BidetHP-BLP-B2 × 0.07 L/s
Bath — unassistedHP-T44LP-T442 × 0.17 L/s
Bath — assistedHP-T46LP-T462 × 0.17 L/s

The AFL values are Arrow’s suggested cartridge selections from the original tutorial, not regulatory flow requirements.

Actual selection must take account of the valve’s certification, available pressure, required flow rate and intended application.

TMV5213 Kit

Arrow Valves’ TMV5213 Kit 6 incorporates a thermostatic mixing valve with AFL Servicing Valves and test-point arrangements.

The original tutorial identifies serviceable 180 µm strainer cartridges and optional flow-limiting cartridges.

These allow the designer to combine isolation, filtration and flow control within the mixing assembly.

Controlling Legionella Risk

Temperature control is an important part of reducing Legionella risk in hot and cold-water systems.

HSE guidance recommends:

  • Cold water: Maintain below 20°C where possible.
  • Stored hot water: Maintain at least 60°C.
  • Distributed hot water: Reach at least 50°C within one minute at outlets, or 55°C in healthcare premises.

These temperatures refer to water system hygiene and should be considered separately from the final mixed-water temperature required for scalding protection.

For installations incorporating TMVs, the temperature of the hot supply should be checked upstream of the mixing valve.

Mixed-water pipework should be kept as short as practicable to reduce stagnation and bacterial growth.

Temperature Measurement and Commissioning

TMVs must be commissioned according to the manufacturer’s instructions and the requirements applicable to the installation.

The original Arrow tutorial recommends using a digital probe thermometer with a refresh rate of at least four readings per second.

The following measurements should be considered:

Cold-water temperature

Measure the cold-water supply, aiming for below 20°C where possible.

Hot-water temperature

Measure the hot supply, using the appropriate test point where provided.

The temperature must be sufficient to maintain the hot-water hygiene requirements while allowing the TMV to operate correctly.

Mixed-water temperature

Measure the outlet temperature and adjust the TMV to the specified setting for its application.

The measured temperature should be checked against the appropriate TMV3 designation and any site-specific requirements.

The valve should also be tested for correct operation under the conditions prescribed by the manufacturer and the relevant commissioning guidance.

Summary

When designing bathroom and washroom water systems:

  1. Establish the Fluid Category associated with each bath, shower or bidet installation.
  2. Provide the appropriate Type AUK2 or AUK3 tap gap where a tap-gap arrangement is used.
  3. For Fluid Category 3 shower hoses, use suitable Double Check Valve or Type HC protection where the required tap gap cannot be maintained.
  4. Where a shower hose can reach a WC pan or bidet, provide Fluid Category 5 protection unless a compliant Type AUK3 tap gap is maintained.
  5. Provide appropriate Fluid Category 5 protection for ascending spray bidets and ablution hoses.
  6. Ensure both hot and cold supplies are protected against contamination.
  7. Select and commission TMVs for the intended application and scalding risk.
  8. Maintain appropriate hot and cold water temperatures to reduce microbial growth.
  9. Confirm any shared or zone-protection arrangements with the local water undertaker.

Downloads

Related Insights

Relevant field notes, audit learnings and specification articles.

Tools

Calculators and lookup tools that support this guide.

Applications

Where this regulation topic most commonly appears in real buildings and systems.

Products

Product families commonly specified against this guide.

Quick Links

Downloads

3 documents

Related insights

4 articles

Related tools

1 tool

Applications

3 sectors

Need help specifying?

Our technicians can walk the current risk, the required device, and the assembly that satisfies AIM.

Regulation guide

Insights on

Showers, Baths & Bidets

Tools & calculators

Calculate, look up, decide