| Property | Value |
|---|---|
| WC maximum flush volume | 6 litres |
| WC dual-flush reduced volume | No more than two-thirds of the full flush |
| Urinal pressure flushing valve | No more than 1.5 litres per bowl or position per operation |
| Automatic urinal cistern — single bowl | 10 L/hour maximum filling rate |
| Automatic urinal cistern — multiple bowls | 7.5 L/hour per bowl, stall or 700 mm slab width |
The Water Regulations establish requirements for WC and urinal flushing, backflow prevention and water conservation in washrooms.
Modern flushing systems can operate without conventional flushing cisterns, using pressure flushing valves supplied from the mains or a boosted cold-water system.
However, the selected arrangement must meet the requirements for water consumption, backflow protection and the intended application.
WC Flush Volumes
Schedule 2, paragraph 25 limits the maximum volume of a WC flush to 6 litres for new installations.
Dual-flush systems are permitted, provided:
- The full flush does not exceed 6 litres.
- The reduced flush does not exceed two-thirds of the full flush volume.
For example, a WC with a 6-litre full flush can have a reduced flush of no more than 4 litres.
WC pans and flushing devices must also comply with the relevant Regulator-approved specifications and provide effective clearance of the pan.
Methods of Flushing WC Pans
Several flushing arrangements are available.
Siphonic Flushing Cisterns
Traditional siphonic cisterns use a siphon mechanism to release the stored water into the WC pan.
This arrangement has been widely used in the UK because the siphon does not rely on a conventional sealing valve at the cistern outlet, reducing the risk of continuous leakage through a failed outlet seal.
However, siphonic flushing mechanisms generally require more physical effort to operate than some modern alternatives.
Mechanical Outlet Valves
Mechanical outlet valves, commonly known as drop or flap valves, allow water to leave the cistern when the flushing mechanism is operated.
These can be activated manually or electronically, including through touch-free sensors.
Unlike a siphonic mechanism, these valves rely on a seal to prevent water escaping between flushes.
Damage, wear or debris around the seal can lead to continuous leakage into the WC pan. Because many cisterns incorporate internal overflows, this leakage can be difficult to identify.
Pressure Flushing Cisterns
Pressure flushing cisterns use the incoming water pressure to compress air within a pressure vessel.
When operated, the stored energy increases the pressure and velocity of the flushing water.
This provides an alternative to a conventional gravity-operated cistern.
Pressure Flushing Valves
Pressure flushing valves allow WC pans to be flushed without a conventional flushing cistern.
The valve releases a predetermined volume of water and can be operated manually or automatically.
For installations in England and Wales, pressure flushing valves must not be installed in houses.
In non-house buildings, a minimum flow rate of 1.2 L/s must be available at the appliance, and the flushing arrangement must incorporate suitable backflow protection.
These requirements make the available supply pressure, flow rate and pipework design important considerations.
Backflow Protection for WCs and Urinals
The contents of WC pans and urinals are classified as Fluid Category 5, representing a serious health risk.
Suitable backflow protection is therefore required to prevent contaminated water entering the wholesome water supply.
Three arrangements discussed in this tutorial are:
- Type AUK1 interposed cistern.
- Type DC pipe interrupter, where suitable for the backflow risk.
- Break tank incorporating a Type AB air gap.
These arrangements have different operating requirements and are not interchangeable in every installation.
Type AUK1 Interposed Cistern
A conventional WC flushing cistern can form a Type AUK1 arrangement where the inlet incorporates a suitable Type AG air gap and the required separation is maintained between the cistern and WC pan.
A Type AUK1 arrangement provides protection against Fluid Category 5 back-siphonage risks, subject to the relevant installation requirements.
It can be supplied from a supply pipe or an appropriate distributing pipe without requiring an additional backflow prevention device solely for the WC pan, provided the complete arrangement complies.
A servicing valve must be installed on the cistern inlet pipe.
In some circumstances, alternative Fluid Category 3 protection at the inlet to a WC flushing cistern can be considered following a specific assessment by the local water undertaker. This should not be assumed to be generally acceptable.
Type DC Pipe Interrupter
A Type DC pipe interrupter is a non-mechanical backflow prevention device that protects against Fluid Category 5 back-siphonage.
It incorporates a nozzle and permanently open atmospheric air inlets.
If the pressure upstream falls and creates a vacuum, the open air inlets prevent contaminated water from being drawn back into the supply.
A Type DC arrangement does not provide backpressure protection.
It must also meet specific installation requirements:
- Installed vertically, with water flowing downwards.
- Atmospheric air inlets must remain permanently unrestricted.
- No flow control valve is permitted downstream.
- The required clearance between the air inlets and receiving appliance must be maintained.
For urinals, the Type DC arrangement must be installed at least 150 mm above the sparge outlet.
For WCs in England and Wales, the current Water Regs UK guidance specifies at least 300 mm above the spill-over level. In Scotland, the corresponding minimum is 150 mm.
The requirements of the relevant water undertaker should be confirmed before installation.
Arrow Valves’ DC257 Pipe Interrupter is intended for suitable Fluid Category 5 back-siphonage applications, including direct urinal flushing.
Type AB Air Gap and Booster Set
Where a pressure flushing arrangement requires Fluid Category 5 protection against both back-siphonage and backpressure, a break tank incorporating a Type AB air gap can provide the necessary separation.
The air gap physically separates the incoming wholesome water supply from the downstream distribution circuit.
A booster pump can then restore the pressure required for flushing.
Arrow Valves’ Boost-A-Break® (BTAB) combines a Type AB break tank and booster pump within a packaged unit.
This can be considered for washroom installations requiring a dedicated protected supply to flushing valves.
Distributing Pipework
A dedicated distributing pipe from a suitable storage cistern can supply multiple WCs and urinals, provided the arrangement satisfies the relevant backflow requirements.
However, a distribution circuit intended for WC or urinal flushing must not automatically be used to supply handbasins or other appliances.
The potential for cross-contamination must be considered.
Where the same storage cistern supplies other types of fittings, separate distributing pipework and suitable protection arrangements must be provided.
The proposed design should be checked against the intended uses and the local water undertaker’s requirements.
Bidets and Ablution Hoses
Bidets incorporating ascending sprays and hoses used for personal cleansing next to WCs present Fluid Category 5 contamination risks.
Both hot and cold water supplies require suitable protection.
Where a hose or spray outlet can reach contaminated water within the WC pan or bidet, an appropriate Fluid Category 5 arrangement is required.
A Type AB air gap can provide protection against both back-siphonage and backpressure.
Water used for personal cleansing must also be appropriate for that purpose. A water circuit supplying WC or urinal flushing must not automatically be treated as suitable for personal washing.
Arrow Valves’ BTHW Ablution Unit provides point-of-use Fluid Category 5 backflow protection and a warm-water supply for suitable ablution hose and bidet installations.
The relevant hot-water temperature controls and installation requirements must also be considered.
Regulator-Approved WC Flushing Arrangements
WC pans and their flushing devices must satisfy the applicable Regulator-approved specifications.
It is important to establish that the selected flushing arrangement is compatible with the WC pan and capable of providing effective flushing within the permitted water volume.
A compliant backflow protection arrangement does not, by itself, establish that the WC flushing system meets all other requirements.
Urinal bowls and flushing arrangements have different applicable requirements.
Urinal Flushing
Urinals can be flushed either through a conventional flushing cistern or by a pressure flushing valve connected to a supply or distributing pipe.
Whichever arrangement is used, appropriate Fluid Category 5 backflow protection must be provided.
Flushing Without a Cistern
A urinal can be flushed directly from the mains or a suitable boosted cold-water circuit using a pressure flushing valve and Type DC pipe interrupter.
A typical electronically controlled arrangement includes:
- A supply pipe providing adequate pressure and flow.
- A solenoid-operated flushing valve.
- A Type DC pipe interrupter.
- A suitable connection to the urinal sparge outlet.
- An electronic sensor and controller.
The sensor detects use of the urinal, and the controller operates the flushing valve for a selected period.
This provides an individual flush rather than flushing several urinals simultaneously.
Maximum Urinal Flush Volume
Schedule 2, paragraph 25 permits pressure flushing valves for urinals where the flush volume does not exceed 1.5 litres per bowl or position for each operation.
The original Arrow tutorial describes approximately 1 litre as a typical individual flush volume, subject to effective operation and the selected fittings.
The flushing system must provide an appropriate wash of the urinal while controlling water consumption.
Urinal Flushing from a Cistern
A conventional urinal flushing arrangement uses a cistern positioned above one or more urinal bowls.
The cistern fills with water and releases its contents through a flushing mechanism when the required water level is reached.
Cisterns can be supplied continuously at a restricted rate or through controlled filling arrangements.
The principal water conservation issue is preventing unnecessary flushing when the urinals are not in use.
Automatic Cistern Filling Rates
Schedule 2, paragraph 25 sets out water consumption requirements for automatically operated urinal flushing cisterns.
The requirements are deemed satisfied where the filling rate does not exceed:
- 10 litres per hour for a cistern serving a single urinal.
- 7.5 litres per hour per bowl, stall or 700 mm width of urinal slab for a cistern serving two or more urinals.
The filling arrangement must also provide suitable control to avoid unnecessary operation when the urinals are not being used.
Urinal Flushing Controls
Several control methods can reduce water consumption.
Time-Controlled Filling
A time switch can prevent the cistern from filling outside selected operating hours.
This reduces water consumption during periods when the building is unoccupied.
However, it does not necessarily prevent unnecessary flushing during occupied hours.
Hydraulic Impulse Controls
Hydraulic impulse controls detect water use elsewhere on a connected circuit and use that activity to initiate or regulate flushing.
These arrangements depend on the expected use of the associated fittings.
For example, a system relying on handbasin use may not operate as intended if the associated water supply is not used.
Electronic Sensors
Electronic sensors can activate flushing after a urinal has been used.
Depending on the system design, they can control either a conventional flushing cistern or an individual pressure flushing valve.
This allows flushing to be more closely linked to actual use.
Individual Urinal Flushing and Water Conservation
A conventional cistern serving several urinals can flush every bowl at the same time, even if only one has been used.
Individual pressure flushing valves allow each urinal to be flushed separately.
Potential benefits include:
- Reduced water consumption.
- Flushing based on individual use.
- No conventional flushing cistern or associated overflow.
- More compact pipework arrangements.
- Adjustable flushing volume and operating controls.
- Individual isolation for maintenance.
The original Arrow tutorial provides an illustrative comparison between uncontrolled cistern flushing, a controlled cistern and individual urinal flushing.
The underlying principle remains relevant: flushing only the urinal that has been used can substantially reduce water consumption compared with repeatedly flushing an entire group.
The financial savings depend on usage frequency, flush volumes, control settings and current water and sewerage charges.
WC Cistern Overflows and Warning Pipes
WC flushing cisterns must incorporate a warning pipe or another arrangement providing equivalent warning of a fault, where required by Schedule 2, paragraph 25.
Traditional external warning pipes make an overflow visible outside the cistern.
Many modern WC cisterns instead use an internal overflow, where excess water passes into the WC pan.
These arrangements can be acceptable, but they create an important maintenance concern.
If a float valve or outlet seal fails, water can continuously enter the pan without an obvious external warning.
Possible alternatives and additional measures include:
- Visible overflow indicators.
- Audible fault warnings.
- Mechanical systems that indicate a fault by preventing normal operation.
- Automatic controls that stop the incoming water when the level rises above the intended operating level.
A serviceable strainer upstream of the cistern inlet valve can also help prevent debris from interfering with its operation.
Arrow Valves’ AFL Servicing Valve can incorporate a strainer cartridge, providing isolation and filtration in one fitting.
Handbasins
Cold-water taps intended to supply drinking water must receive wholesome water.
Where non-wholesome cold water is provided at a tap, appropriate labelling is required to prevent accidental consumption.
In non-house premises, taps supplying water that is not suitable for drinking should be clearly identified.
Washbasins can also contribute to unnecessary water consumption where taps are left running.
Where a plug is not provided, Schedule 2, paragraph 28 contains specific requirements and exemptions, including arrangements incorporating self-closing taps.
Automatic Flow Limiting Valves can help control the maximum water flow at washbasins while servicing valves allow individual fittings to be isolated for maintenance.
Hose Union Taps in Washrooms
Hose union taps used for washroom cleaning can present Fluid Category 5 risks, particularly where hoses could come into contact with contaminated water.
The appropriate level of protection depends on the intended use and the water undertaker’s risk assessment.
A break tank incorporating a Type AB air gap can provide Fluid Category 5 protection.
The original Arrow tutorial describes the use of a common protected circuit supplying WC and urinal flushing and a hose union tap in the toilet area, subject to the relevant protection and distribution requirements.
Where a gravity-fed arrangement is used, a suitable distributing pipe from a protected cistern can also be considered.
Preventing Unauthorised Use
A hose union tap in a washroom is not intended to provide drinking water and should be labelled accordingly.
It is also sensible to consider restricting access to prevent misuse.
Arrow Valves offers:
- HUTB: A hose union tap housed inside a lockable stainless-steel enclosure.
- HUD Detach-A-Tap: A removable wall-mounted hose union tap arrangement designed to prevent unauthorised use when the outlet has been removed.
These arrangements help control access, but suitable backflow protection must still be provided for the intended application.
Summary
When designing washroom water systems:
- Ensure WC flushing volumes comply with the 6-litre maximum and relevant dual-flush requirements.
- Select flushing devices suitable for the WC or urinal and the available pressure and flow.
- Provide appropriate Fluid Category 5 backflow protection for WC and urinal flushing arrangements.
- Use Type DC pipe interrupters only where their operating limitations and installation requirements are satisfied.
- Consider individual urinal flushing or suitable controls to prevent unnecessary water consumption.
- Ensure WC cistern overflows and warning arrangements provide adequate indication of faults.
- Provide servicing valves for cisterns and other fittings as required.
- Assess bidets, ablution hoses and washroom hose union taps separately for their backflow risks.