Glossary

Glossary

Plain-language definitions of the terms used across this Knowledge Hub — from air gaps and BA devices to WRAS, AIM and HTM 04-01.

Popular Searches

A

Double check valve

Two independently acting check valves in series (ED). Permitted for Fluid Category 3 only; not for heating filling loops on non-house systems.

Type B air gap

Air gap with weir overflow (AB). Common on break tanks.

Type A air gap

Unrestricted air gap (AA). Highest form of backflow protection. Mandatory for Fluid Category 5.

Spillover level

The level at which water would overflow from a receiving vessel. Used to measure air gap height.

Reduced pressure zone

The chamber between the two checks of an RPZ, held at a pressure lower than upstream so any leak discharges rather than passing.

Reduced pressure zone (RPZ) valve

A mechanical backflow prevention assembly that uses two check valves with a differential-pressure relief valve to provide Category 4 protection against both back-pressure and back-siphonage.

Fluid Category 4

A fluid that represents a significant health hazard because of the concentration of toxic substances, including chemical or radioactive.

Fluid category

Classification of a fluid according to the hazard it represents to health if it entered the wholesome supply. Defined in Schedule 2 Table.

EA device

EN 1717 designation for a controllable check valve (single).

ED device

EN 1717 designation for a verifiable double check valve assembly.

Air gap

Unobstructed vertical distance between the lowest point of a water inlet and the spillover level of a receiving vessel. Type AA, AB, AD, AF, AG.

DC pipe interrupter

Device with atmospheric ports that break siphonage. Limited to low-hazard, unrestricted-discharge applications.

Check valve

Single or double mechanical device that allows flow in one direction only. Double check (ED) is Category 3 maximum.

Category 1–5

Five fluid risk classes in BS EN 1717 / Schedule 2. Category 1 is wholesome water; Category 5 is a serious health hazard (pathogenic organisms).

Break tank

Storage cistern that physically separates a wholesome supply from a downstream system via an air gap. Required for Category 5.

Back-siphonage

Reversal of flow caused by a reduction of pressure in the supply, drawing downstream fluid back into the wholesome system.

Back-pressure

Pressure in the downstream system exceeding the supply pressure, forcing fluid back toward the wholesome main.

BA device

EN 1717 designation for a reduced pressure zone (RPZ) valve. Provides Fluid Category 4 protection against back-pressure and back-siphonage.

AUK3

UK-specific air gap arrangement combining a Type A air gap with a weir overflow. Used on break tanks serving Category 5.