| Property | Value |
|---|---|
| House heating circuit | Fluid Category 3* |
| Non-house heating circuit | Fluid Category 4* |
| House vented system | Type AG air gap |
| Non-house vented system | Type AB air gap |
| Vented system expansion allowance | At least 4% of the primary circuit volume |
| Expanded water level | At least 25 mm below the warning pipe overflow level |
| Type CA device | Protection up to Fluid Category 3 |
| Type BA (RPZ) device | Protection up to Fluid Category 4 |
Heating systems are normally either vented or unvented (sealed). Both arrangements require suitable backflow protection to prevent water from the heating circuit entering the wholesome water supply.
The level of protection depends on the Fluid Category assigned to the heating circuit and how the system is filled.
Types of Heating Systems
Vented systems
A vented heating system uses a feed and expansion cistern (F&E tank). The cistern supplies water to the heating circuit by gravity and accommodates the thermal expansion of water as it heats.
Backflow protection is provided by a suitable air gap in the cistern. This arrangement is less common in new installations.
Unvented (sealed) systems
Sealed heating systems remain under pressure and use an expansion vessel rather than an F&E cistern to accommodate thermal expansion.
Backflow protection is normally provided by a mechanical device or an air gap during filling.
Fluid Categories
Water in a heating circuit can contain dissolved metals, flux and chemical inhibitors. These substances can present a contamination risk if the water flows back into the wholesome supply.
A typical house primary heating circuit is considered Fluid Category 3.
Non-house heating systems are normally treated as Fluid Category 4 because of the potential quantity and concentration of contaminants within the system.
The local water undertaker can assess the installation and determine whether another Fluid Category is appropriate, taking account of factors such as the system size and chemicals used.
However, identifying the Fluid Category is only the first step. The filling arrangement must also comply with the requirements for that particular application.
For example, although a typical house heating circuit is Fluid Category 3, a permanently connected filling loop protected only by a Double Check Valve is not an acceptable arrangement.
House Heating Systems
Vented Primary Heating Systems
The feed and expansion cistern in a house should incorporate a Type AG air gap, formerly known as Type B.
In practical terms, the tutorial describes achieving this using a BS 1212 Part 2 float valve.
A ½″ BS 1212 Part 1 float valve is not suitable for this arrangement because its closing water level cannot be adjusted to meet the relevant requirements.
BS 1212 Part 2 valves incorporate a brass body, adjustable water level and an up-and-over outlet arrangement.
The warning pipe (overflow) should have a minimum bore of 19 mm and be positioned below the supply pipe serving the float valve.
Unvented (Sealed) Primary Heating Systems
Many houses and individually occupied flats use sealed heating systems, including those served by combination boilers.
A temporary filling loop with a suitable Double Check Valve can be used where the heating circuit is assessed as Fluid Category 3.
The backflow prevention device must be positioned upstream of the flexible filling hose.
The filling loop must be disconnected after filling or replenishing the heating system.
It is good practice to remove the flexible hose completely. However, disconnecting one end is also acceptable where the disconnection is between the hose and the backflow prevention device on the supply pipe.
This arrangement maintains backflow protection if the flexible hose is subsequently used for another purpose.
Permanently Connected Filling Arrangements
An alternative to a removable filling loop is a Type CA backflow prevention device.
A Type CA device provides protection against contamination risks up to Fluid Category 3 and can remain permanently connected to the heating system.
Arrow Valves offers the CA297, which can be incorporated into a filling assembly alongside servicing valves, a strainer and pressure-reducing equipment.
Unlike a temporary filling loop protected by a Double Check Valve, a suitable Type CA arrangement does not require disconnection after filling.
Non-House Heating Systems
Non-house heating systems are generally treated as Fluid Category 4 unless the local water undertaker determines that a different level of protection is appropriate.
This applies to both vented and sealed arrangements.
For Fluid Category 4, suitable backflow protection can be provided through a Type BA device (RPZ valve) or an appropriate air gap arrangement.
Vented Primary Heating Systems
Non-house heating systems containing corrosion inhibitors and other potentially toxic substances normally require Fluid Category 4 backflow protection.
For vented systems, the tutorial recommends a Type AB air gap.
Storage cisterns must meet the relevant requirements, including the provision of a lid under Schedule 2, paragraph 16.
A Type AB air gap incorporates a rectangular weir overflow arrangement to BS EN 13077 and provides protection against Fluid Category 5 contamination risks.
The local water undertaker can assess the system and its chemical contents to determine the appropriate Fluid Category.
Allowing for Thermal Expansion
A feed and expansion cistern must have sufficient spare capacity to accommodate the expansion of water as the heating system reaches its operating temperature.
The cistern should provide an expansion allowance of at least 4% of the total primary circuit volume, not simply 4% of the cistern capacity.
When the heating system is fully expanded, the water level should remain at least 25 mm below the warning pipe overflow level.
For large heating systems, providing this allowance can result in the normal water level sitting more than a metre below the float valve.
Insufficient expansion capacity can cause heating water and its chemical inhibitors to overflow as the system heats.
When the system cools, the lost water is replaced with fresh mains water. This dilutes the remaining inhibitor and introduces dissolved minerals, potentially increasing the risk of scaling, corrosion and system damage.
The cistern must therefore accommodate thermal expansion without wasting water or chemicals.
Non-House Unvented (Sealed) Primary Heating Systems
Sealed heating systems are now common in commercial and other non-house applications.
These systems are normally treated as Fluid Category 4 and should be filled using a suitable Type BA device or an appropriate air gap arrangement.
Small pressurisation units often incorporate an electromagnetic piston pump designed to maintain system pressure rather than provide the initial filling flow required.
For this reason, filling and pressurisation requirements should be considered separately.
Filling Through a Break Tank
The primary circuit can be filled from a break tank incorporating a Type AB air gap, together with a pump capable of providing the required filling flow and pressure.
A multistage centrifugal pump is commonly used for this purpose.
Arrow Valves offers the Midi-Fill Digital (MFD), a pressurisation unit incorporating Fluid Category 5 protection through a Type AB air gap.
This provides an alternative to directly filling the heating system through mechanical backflow protection.
Filling Through a Type BA Device
A Type BA device, commonly known as an RPZ valve, provides backflow protection against Fluid Category 4 contamination risks.
A BA device can be installed upstream of a conventional pressurisation unit, allowing a suitable filling connection to remain permanently connected where the arrangement complies with the relevant requirements.
Alternatively, the BA device can be incorporated into the filling arrangement where the pressurisation unit provides appropriate air gap protection.
The Type BA installation requires the necessary supporting fittings, including suitable isolating valves, a fine strainer and appropriate pressure control.
Where a non-house heating circuit has been specifically assessed and accepted as Fluid Category 3, a removable filling loop with a Double Check Valve could be permitted.
A Type CA device provides an alternative Fluid Category 3 arrangement that can remain permanently connected.
A filling loop protected only by a Double Check Valve must not be used for a heating circuit classified above Fluid Category 3.
Using an RPZ Valve for Pressurisation
A Type BA device can also form part of an arrangement that fills and maintains the pressure of a sealed heating system directly from the wholesome water supply.
This can remove the need for a conventional pressurisation unit, provided the water supply has sufficient pressure and the correct controls are installed.
It is essential to prevent the heating system from becoming over-pressurised.
A Pressure Reducing Valve (PRV) or another suitable pressure control arrangement is therefore required.
Pressure Reducing Valves
Pressure Reducing Valves generally operate effectively when supplied with clean water.
However, debris trapped between the valve seat and sealing washer can prevent the valve from closing tightly at its set pressure.
This is particularly important in sealed heating systems, where there is little or no regular water draw-off.
Failure to control the pressure can cause over-pressurisation and potentially operate the boiler’s high-pressure cut-out.
A fine strainer installed upstream of the PRV helps reduce this risk.
Some PRVs incorporate integral strainers, although these can be too coarse to provide adequate protection.
The Arrow Valves PRV536 incorporates a stainless-steel seat as an alternative to the plastic seats found in many conventional PRVs.
Solenoid Valve Control
An alternative method of pressure control uses a solenoid valve operated by a pressure switch.
The solenoid valve closes when the required pressure is reached.
This arrangement can provide positive closing control, with fine filtration helping protect the valve against debris.
Arrow Valves offers the Autofill pressurisation unit, incorporating solenoid controls and the appropriate backflow protection within a complete filling and pressurisation assembly.
Supply Pressure
The available supply pressure must be sufficient to fill and maintain the heating system at its required cold-fill pressure.
Where mains pressure is insufficient, the Autofill can be connected to an existing boosted wholesome water supply, provided the selected arrangement is suitable.
Where a boosted cold-water supply is unavailable, Arrow Valves offers the AFP Autofill with an integral pump.
The tutorial describes an optional electromagnetic pump capable of boosting pressure up to 5 bar.
The Autofill arrangement allows the system to be initially filled using the available supply pressure, with the pump subsequently operating when additional pressure is required.
A tankless arrangement also avoids the need to store filling water in an open cistern and the associated risk of debris accumulating in the stored water.
Type BA (RPZ Valve) Installation Requirements
Type BA devices must be suitable for their intended application and installed in accordance with the requirements of the local water undertaker.
RPZ valves provide protection against Fluid Category 4 risks, but their effectiveness depends on correct installation, commissioning, operation and maintenance.
The RPZ Approved Installation Method (AIM), January 2025 Issue 3 sets out the relevant requirements.
These include:
- Notification and consent from the local water undertaker.
- Suitable isolating valves and upstream strainer.
- Appropriate access and clearance for inspection, servicing and testing.
- Suitable arrangements for water released through the relief valve.
- Protection against freezing, damage and interference.
- Commissioning and ongoing compliance testing.
The RPZ valve must be tested by a competent tester before being brought into service.
Further compliance testing is required at intervals specified by the local water undertaker, normally annually or more frequently where required.
The installation should also account for the minimum available supply pressure and the pressure differential required by the selected device.
For detailed installation requirements, refer to the current Water Regs UK RPZ guidance and the RPZ Approved Installation Method.
Chemical Dosing and Water Monitoring
Dose & Fill
Filling and pressurising a heating system is only part of maintaining its operation.
Sealed heating systems commonly contain corrosion inhibitors. Each time mains water is added to replace water losses, the inhibitor becomes diluted.
A Dose & Fill unit combines system filling and pressurisation with automatic chemical dosing.
It measures the volume of make-up water entering the heating system and adds the required quantity of inhibitor to maintain the selected concentration.
Arrow Valves’ Dose & Fill (DF) incorporates the Midi-Fill Digital pressurisation unit and provides Fluid Category 5 backflow protection.
The tutorial specifies an adjustable inhibitor concentration of 0.5%–4%.
Water Meters
A water meter can be useful on larger non-house heating systems, whether vented or sealed.
Most systems require a DN15 or DN20 supply, and a meter with a digital display showing individual litres is recommended.
A meter allows the installer or operator to:
- Determine the system volume during initial filling.
- Monitor the quantity of water added subsequently.
- Identify unexpected make-up water consumption that could indicate a leak.
- Calculate the amount of chemical inhibitor required.
The Midi-Fill Digital includes an integral electronic water meter.
The Autofill can be supplied with a volumetric water meter, model WMV.
Dosing Pots
A dosing pot provides a means of introducing liquid chemicals, such as corrosion inhibitors and antifreeze solutions, into sealed heating and chilled-water circuits.
Arrow Valves’ DP Dosing Pot is supplied with five full-bore servicing valves, a safety check valve, funnel and mounting brackets.
Expansion Vessels
Expansion vessels accommodate the thermal expansion of water within sealed heating systems.
Arrow Valves’ EVCP range is suitable for primary circuit, unvented heating applications and is available with 4, 5 or 6 bar pressure ratings depending on size.
The EVUP range is available for higher-pressure requirements, up to 10 bar. It is primarily intended for wholesome water applications but can also accommodate expansion.
Summary
When designing or maintaining a heating system filling arrangement:
- Identify the Fluid Category and select suitable backflow protection.
- For house heating systems assessed as Fluid Category 3, a temporary filling loop with Double Check Valve protection can be used, provided the hose is disconnected after filling.
- Where a permanent Fluid Category 3 filling connection is required, consider a suitable Type CA device.
- For non-house systems assessed as Fluid Category 4, use suitable Type BA protection or an appropriate air gap arrangement.
- Ensure adequate pressure and flow are available for initial filling and ongoing pressurisation.
- Install, commission and regularly test Type BA devices in accordance with the RPZ AIM and the water undertaker’s requirements.
- Provide sufficient expansion capacity for vented heating systems and account for inhibitor concentration and make-up water consumption.