Regulation guide

Schedule 1; Schedule 2, paragraphs 15 and 29

24 Nov 2026

10

Clothes & Dishwashing

PropertyValue
Domestic washing machines and dishwashersFluid Category 3
Non-domestic washing machines and dishwashersFluid Category 4*
High-risk applicationsFluid Category 5
Type BA (RPZ valve)Protection up to Fluid Category 4
Type AB air gapProtection up to Fluid Category 5

Most water fittings incorporate backflow protection, either through a mechanical device or an arrangement built into their design.

Schedule 2, paragraph 15 of the Water Supply (Water Fittings) Regulations 1999 requires water systems to incorporate adequate protection against backflow from appliances, fittings and processes.

For example, many taps provide point-of-use protection through the air gap between the tap outlet and the spill-over level of the receiving appliance. The relevant measurement is taken to the spill-over level, regardless of whether the appliance has an overflow pipe.

WC cisterns also incorporate backflow protection through an appropriate air gap associated with the float valve.

Washing machines and dishwashers require the same consideration, but the level of protection depends on how and where they are used.

Washing Machines and Dishwashers

Most domestic clothes washing machines and dishwashers are manufactured with integral backflow protection suitable for Fluid Category 3.

In normal household applications, the contamination risk is typically classified as Fluid Category 3. Where the appliance incorporates suitable protection for the intended installation, additional external backflow protection is not normally required.

However, a machine designed for domestic use is not necessarily suitable for commercial or higher-risk applications.

The important consideration is not simply the appliance, but the potential contaminants introduced by the items being washed.

Fluid Categories

Fluid Categories identify the potential level of contamination risk.

Fluid CategoryRiskBackflow protection examples
5Serious health hazardType AA/AB air gaps
4Significant health hazardType BA (RPZ valve)
3Slight health hazardDouble Check Valve (EC/ED)
2Water with altered taste, odour or appearanceSingle Check Valve (EA/EB)
1Wholesome drinking waterNo additional protection required

Fluid Category 3 — Domestic Applications

Domestic washing machines normally wash clothing contaminated with everyday dirt, detergents and other substances.

The quantities and concentrations involved in normal household use generally result in a Fluid Category 3 classification.

The appliance must incorporate suitable backflow protection or be supplied through an appropriate external arrangement.

Fluid Category 4 — Non-Domestic Applications

The same washing machine installed in a commercial laundry, catering premises or another non-domestic environment can present a higher contamination risk.

Water used in these applications can contain greater concentrations of chemicals and other contaminants.

These installations are typically considered Fluid Category 4, requiring a higher level of backflow protection than that provided by many domestic appliances.

Fluid Category 5 — High-Risk Applications

In healthcare premises, nursing homes and other higher-risk environments, washing machines can be used to clean items contaminated with bodily fluids, human waste or other potentially harmful substances.

These applications can present a Fluid Category 5 risk.

A washing machine used to clean heavily contaminated bedding in a nursing home, for example, can require a different level of protection from the same appliance washing ordinary household clothing.

The Fluid Category must reflect the highest reasonably foreseeable contamination risk associated with the intended use.

Where necessary, the classification and required level of protection should be confirmed with the local water undertaker.

Fluid Category 4 Backflow Protection

A Type BA device, commonly known as a Reduced Pressure Zone (RPZ) valve, provides mechanical backflow protection for risks up to Fluid Category 4.

It is a suitable option for many commercial washing machine and dishwasher installations where Fluid Category 4 protection is required.

A suitable air gap arrangement can also provide the necessary protection.

Point-of-Use Protection

Designers sometimes propose supplying several appliances from a separate non-drinking water distribution circuit, protected at its source by a break tank with a Type AB air gap.

However, providing protection at the source does not automatically remove the requirement for suitable point-of-use protection.

Schedule 2, paragraph 15 requires each appliance, fitting or process to have adequate protection against backflow.

This is important because contamination can occur between appliances connected to the same distribution pipework, even where the incoming water supply is already separated from the wholesome water supply.

Washing Machines and Dishwashers on the Same Supply

Consider a commercial washing machine and dishwasher connected to the same pipework.

The dishwasher is performing its final rinse while the washing machine contains heavily contaminated washing water.

If backflow conditions occur, contaminated water from the washing machine could enter the shared pipework and reach the dishwasher.

A separate Type BA device serving each appliance can prevent this cross-contamination.

This illustrates why protecting the incoming supply alone does not necessarily provide adequate protection between different applications.

Zone Protection

A group of appliances performing similar functions can present a different situation.

For example, several clothes washing machines operating within the same laundry may be supplied through a common backflow protection arrangement, subject to the local water undertaker’s assessment and consent.

The original Arrow tutorial describes a single larger Type BA device supplying a group of washing machines.

This type of shared arrangement requires careful consideration of the appliances, their risks and the requirement for individual point-of-use protection.

The local water undertaker should confirm whether the proposed arrangement is acceptable.

Type BA (RPZ Valve) Installation Requirements

Relief Valve and Waste Connection

A Type BA device incorporates check valves and a relief valve within a reduced-pressure zone.

The relief valve operates under specified conditions to prevent potentially contaminated water flowing back into the supply.

Water released from the relief valve must be safely conveyed away without restricting the operation of the device.

The Arrow tutorial identifies the use of a suitable waterless trap as a practical option where a nearby foul-water connection is available, as is often the case with washing machines and dishwashers.

The waste arrangement must comply with the current RPZ Approved Installation Method, including the required air gap and provision for relief valve operation.

Installation and Testing

The RPZ Approved Installation Method (AIM), January 2025 Issue 3, specifies the requirements for installing, commissioning and testing Type BA devices.

These include:

  • Resilient-seat isolating valves.
  • An appropriate upstream strainer.
  • Suitable installation clearances for inspection and maintenance.
  • A compliant relief valve outlet arrangement.
  • Protection against unauthorised interference.
  • Commissioning and periodic testing by a competent RPZ tester.

RPZ valves require testing at intervals specified by the local water undertaker, at least annually.

Arrow Valves supplies 15 mm and 22 mm BA assemblies within compact cabinets, incorporating the necessary valves, strainer and tundish.

Arrow also provides commissioning and testing services through its network of accredited testers.

Strainers

Where a Type BA device protects a group of appliances, the annual volume of water passing through the assembly can be considerable.

A larger-capacity strainer with a semi-automatic or fully automatic back-flush facility can provide a practical alternative to a conventional Y strainer.

Arrow Valves offers the Option F Assembly, incorporating a 100 micron strainer with a semi-automatic back-flush facility.

This arrangement is particularly relevant to commercial laundries and other high-demand installations.

Hot Water Backflow Protection

Hot water used for domestic purposes, including personal washing, should remain suitable for its intended use and be protected from contamination.

Some commercial dishwashers use a hot-water connection, while clothes washing machines can have both hot and cold supplies.

Where Type BA protection is required, the selected valve must be suitable for the water temperature and operating pressure.

The manufacturer’s specifications should be checked before selecting an RPZ valve for a hot-water connection.

Where practical, cold-water filling can simplify the protection arrangement and reduce the risk of scalding during testing or maintenance.

Gravity-Fed Hot Water Supplies

Type BA devices require sufficient available pressure to operate correctly.

Older buildings with gravity-fed hot-water supplies can have insufficient pressure for an RPZ valve to operate as intended.

Where the hot-water supply is gravity-fed and the cold-water supply is at mains pressure, supplying the machine with cold water alone can be a practical alternative, provided the appliance manufacturer permits it.

The machine’s internal heating elements would then heat the water to the required temperature, potentially increasing the cycle time.

Long pipe runs between a hot-water cylinder and an appliance can also reduce the benefit of a hot-fill connection, particularly where the volume of standing water in the pipe is comparable to the machine’s fill volume.

Where a dedicated water-heating plant serves only a group of washing machines, a suitable common supply arrangement may be considered, subject to the required point-of-use and cross-contamination protection.

Fluid Category 5 Protection

Where an appliance presents a Fluid Category 5 risk, suitable protection is required to prevent the serious contamination risk reaching the wholesome water supply.

For healthcare and other high-risk washing applications, the Arrow tutorial recommends a dedicated break tank incorporating a Type AB air gap.

A Type AB air gap provides Fluid Category 5 protection and physically separates the incoming water supply from the potentially contaminated downstream circuit.

An air gap alone does not provide pressurised water. Where the appliance requires a higher pressure than gravity can provide, a suitable pump is required.

Break Tank and Booster Set

Arrow Valves’ Midi-Break® (BTMIDI) combines a break tank with a Type AB air gap and a booster pump.

It provides Fluid Category 5 backflow protection while restoring the pressure required to supply washing machines and dishwashers.

Appliances with Integral Fluid Category 5 Protection

Some commercial washing machines and dishwashers incorporate suitable Fluid Category 5 backflow protection within the appliance.

Where that protection is appropriate for the installation, an additional external backflow prevention arrangement may not be necessary.

The appliance’s certification, installation instructions and declared backflow protection should be checked.

Commercial appliances with higher levels of integral protection can be physically larger and more expensive than typical domestic machines. Their dimensions and suitability should therefore be considered during specification.

Glass Washers

Glass washers in pubs, bars and other catering environments require backflow protection appropriate to the intended use.

Particular attention is required where a flexible spray hose can be submerged in contaminated washing or rinsing water.

The original Arrow tutorial identifies this type of arrangement as a potential Fluid Category 4 risk.

Where Fluid Category 4 protection is required, a Type BA device can provide a mechanical backflow prevention solution.

An appropriate Type AA or AB air gap arrangement can also provide protection, although pumping may be required to restore the necessary supply pressure.

The Arrow tutorial describes the Option B Assembly, incorporating a 15 mm Type BA device within a compact cabinet.

The protection arrangement, including any proposed shared supply to a glass washer and dishwasher, must be confirmed against the actual risk and the local water undertaker’s requirements.

Connecting Hoses and Water Quality

Flexible hoses connecting washing machines and dishwashers to the water supply can affect water quality.

Certain hose materials can release substances that cause undesirable tastes or odours in drinking water.

Pressure fluctuations and other mechanisms can allow affected water to move back towards pipework supplying drinking-water taps.

Connecting hoses should therefore be suitable for contact with drinking water and meet the relevant material requirements, including BS 6920 where applicable.

The original tutorial also describes the use of a Single Check Valve (Type EB) to limit the movement of water from an appliance connection back towards the wholesome supply.

Such protection must be selected according to the actual Fluid Category and the intended purpose. A Single Check Valve does not provide Fluid Category 3, 4 or 5 backflow protection.

The Arrow Valves EB235 / EB20FM235 is identified in the original tutorial as an example of a Type EB check valve.

Flood Protection

A damaged or ruptured flexible hose connecting a washing machine or dishwasher can result in significant water loss and property damage.

The original tutorial gives an approximate appliance supply flow of 0.2 L/s.

Where a hose fails, water can continue flowing until the supply is isolated.

An Automatic Waterstop Valve installed upstream of the flexible hose can reduce the risk by shutting off the supply when excessive flow is detected.

The Arrow Valves AWS20FM is designed to shut off when the flow reaches at least 0.3 L/s.

The suitability of the valve depends on the normal appliance flow and the excess-flow conditions it is intended to detect.

Water Consumption

Schedule 2, paragraph 29 of the Water Supply (Water Fittings) Regulations 1999 sets out requirements for the water consumption of clothes washing machines, washer-driers and dishwashers.

These requirements establish water-use limits linked to the washing load or number of place settings.

The appliance’s stated consumption should be checked against the applicable requirements during specification.

Summary

When specifying or installing clothes washing machines and dishwashers:

  1. Establish the intended use and Fluid Category. The same appliance can present different contamination risks depending on where and how it is used.
  2. Check the appliance’s integral backflow protection. Confirm that it is suitable for the assessed risk.
  3. Provide appropriate point-of-use protection. Do not assume that zone or whole-site protection removes the need to protect individual appliances.
  4. Select a suitable device or arrangement. This could include Type BA protection, a suitable air gap or verified integral protection.
  5. Notify the local water undertaker where required. Confirm the proposed installation and any conditions of consent before work begins.

Downloads

Related Insights

Relevant field notes, audit learnings and specification articles.

Tools

Calculators and lookup tools that support this guide.

Applications

Where this regulation topic most commonly appears in real buildings and systems.

Products

Product families commonly specified against this guide.

Quick Links

Downloads

3 documents

Related insights

4 articles

Related tools

1 tool

Applications

3 sectors

Need help specifying?

Our technicians can walk the current risk, the required device, and the assembly that satisfies AIM.

Regulation guide

Insights on

Clothes & Dishwashing

Tools & calculators

Calculate, look up, decide