Regulation guide

Regulations 4 and 5; Schedule 2, paragraph 15

24 Nov 2026

7

Hose Union Taps

PropertyValue
Domestic garden protectionFluid Category 3 (Double Check Valve)
Non-domestic protectionFluid Category 3, 4 or 5 (subject to risk assessment)
Type AUK2 tap gap20 mm (½″), 25 mm (¾″), 70 mm (larger taps)
Type AUK3 tap gapAt least twice the inlet-pipe bore and no less than 20 mm
Irrigation outlet clearance150 mm above ground where applicable

Hose union taps in non-house installations are among the most debated aspects of backflow protection.

Although the Water Regulations provide a consistent framework, the level of protection required depends on the intended use, surrounding environment and the local water undertaker’s assessment of risk.

Types of Taps

Most basin, sink and bath taps are not designed for hoses. Their outlets sit above the spill-over level, creating a tap gap that provides point-of-use backflow protection.

Two relevant arrangements are:

  • AUK2 (Fluid Category 3): A minimum tap gap of 20 mm for ½″ taps, 25 mm for ¾″ taps and 70 mm for larger taps.
  • AUK3 (Fluid Category 5): An air gap of at least twice the inlet-pipe bore and no less than 20 mm.

Hose union taps do not provide this air gap when a hose is connected.

Any tap capable of accepting a hose, including laboratory taps, requires suitable backflow protection. Non-domestic hose union taps should initially be considered a Fluid Category 5 risk unless the local water undertaker determines that a lower category is acceptable.

Fluid Categories

Backflow protection must be appropriate to the potential contamination risk.

Fluid Categories range from 1, representing wholesome drinking water, to 5, representing a serious health hazard.

Fluid CategoryRiskProtection examples
5Serious health hazardType AA/AB air gap; Type DC pipe interrupter
4Significant health hazardRPZ valve — Type BA
3Slight health hazardDouble Check Valve — Type EC/ED
2Wholesome water with altered taste, odour or appearanceSingle Check Valve — Type EA/EB
1Wholesome drinking waterNo additional protection required

The suitability of each device depends on the installation and the type of backflow risk.

Further information is available from Water Regs UK — Fluid Categories.

House Gardens and Similar Installations — Fluid Category 3

The minimum backflow protection required for a hose union tap used in a typical house garden is a Double Check Valve.

Hose union taps containing two check valve cartridges, now classified as HUK1, are not suitable for new exterior installations.

These arrangements are vulnerable to frost damage. A Double Check Valve should be installed upstream of the hose union tap, inside the thermal envelope of the building where applicable, and protected from freezing.

Arrow Valves’ ED132 is a low head-loss Double Check Valve suitable for appropriate Fluid Category 3 applications.

Where there is no building available to mount a tap, Arrow offers standpipe solutions such as the SPHUD Pillar Standpipe, incorporating a Double Check Valve and a degree of frost protection.

Non-House Installations — Fluid Categories 3, 4 and 5

Hose union taps in offices, factories, schools, recreational areas and other non-house installations require careful consideration.

For design purposes, these installations should initially be treated as Fluid Category 5 risks.

The designer should provide the local water undertaker with details of the proposed installation, including the location and intended use of the tap.

Depending on the assessed risk, suitable protection could include:

  • Fluid Category 3: Double Check Valve (ED device).
  • Fluid Category 4: RPZ valve (BA device).
  • Fluid Category 5: Suitable air gap protection, such as a Type AB break tank arrangement.

Where the proposed use is comparable to a house garden, the water undertaker could accept Fluid Category 3 protection, subject to conditions restricting how the tap is used.

Fluid Category 5 Standpipes

For Fluid Category 5 applications where boosted pressure is unnecessary, Arrow Valves offers the SPFC5 Standpipe as an alternative to a break tank and booster set.

The SPFC5 requires no electrical power and supplies water under gravity, making it suitable for applications such as filling canal boats.

For applications requiring higher pressure, including washdown, a break tank and booster set is generally more appropriate.

What Is Considered Domestic Use?

The Regulations do not define the terms ‘commercial’ and ‘domestic’.

For this guidance, domestic refers to normal household use, including houses, flats and bungalows.

A hose union tap in a non-house garden could be accepted as Fluid Category 3 where its use is comparable to a domestic garden.

For example, this could include above-ground watering using a handheld hose fitted with a self-closing flow control device and disconnected when not in use.

The proposed arrangement should be confirmed with the local water undertaker.

Fluid Category 4 Applications

Where a hose union tap is intended for certain chemical or industrial washdown applications, the water undertaker could assess the installation as Fluid Category 4.

In these circumstances, an RPZ valve (BA device) could provide suitable backflow protection.

Where possible, the RPZ valve should be installed inside the building. External installations require appropriate frost protection, such as an insulated cabinet.

For installations without a suitable building connection, Arrow Valves offers the SPBA Standpipe, incorporating Fluid Category 4 backflow protection.

A higher level of protection can also be provided through a dedicated break tank incorporating a Type AB air gap.

Below-Ground Hose Union Taps

Where a conventional standpipe is unsuitable, Arrow Valves offers the HUBG Below-Ground Hose Union Tap Assembly.

As the outlet is less than 150 mm above ground, the installation requires appropriate Fluid Category 5 protection.

The tutorial specifies supplying the HUBG from a dedicated break tank incorporating a Type AB air gap, such as Arrow’s Boost-A-Break® (BTAB), rather than directly from a supply pipe.

Irrigation

Non-house irrigation installations with outlets less than 150 mm above ground are normally considered Fluid Category 5 risks.

These arrangements commonly require protection through a break tank incorporating a Type AB air gap.

Examples include:

  • Pop-up sprinklers
  • Below-ground hose union taps
  • Drain taps
  • Quick-release couplings
  • Irrigation hoses and ground-level sprinkler heads

Even a sprinkler head resting on a lawn can present a Fluid Category 5 risk because its outlet is less than 150 mm above the ground.

For suitable domestic or commercial irrigation applications without fertiliser or insecticide additives, Arrow Valves offers the SPTB Miniature Standpipe, with its outlet positioned above the 150 mm threshold.

The appropriate level of protection remains subject to the installation’s risk assessment and the local water undertaker’s requirements.

Installation Considerations

Backflow protection is not the only consideration when installing hose union taps.

Frost protection, misuse and vandal resistance should also be addressed.

Where possible, avoid unnecessary underground pipe connections.

Where no wall is available for mounting a hose union tap, a standpipe can provide a practical alternative.

Arrow Valves’ SPED Standpipe incorporates:

  • ED132 low head-loss Double Check Valve
  • Servicing valve
  • Lockable enclosure
  • Optional pile for installation in soft ground

An unsecured or damaged hose union tap can lead to considerable water wastage.

Where a standpipe enclosure is unsuitable, a lockable wall-mounted tap can provide additional protection against unauthorised use.

Conventional hose union taps are often fitted into wall plates using parallel male threads and PTFE tape, leaving them vulnerable to removal or damage.

The Arrow Valves HUTB provides an alternative, housing the hose union tap inside a lockable stainless-steel enclosure.

Water Conservation

Handheld hoses should be fitted with a control device, such as a self-closing trigger, to help prevent unnecessary water wastage.

A flow control device is not a recognised form of backflow protection.

Labelling

In non-household premises, taps should be clearly labelled where necessary to distinguish drinking water supplies from non-drinking water supplies.

This helps prevent inappropriate use and supports safe operation of the installation.

Summary

When specifying or installing hose union taps:

  1. Do not specify HUK1 taps for new exterior installations.
  2. For irrigation and ground-level applications, maintain at least 150 mm outlet clearance where applicable, or provide appropriate Fluid Category 5 protection.
  3. Protect installations against frost, damage and misuse.
  4. Confirm notification and backflow protection requirements with the local water undertaker.
  5. Ensure the client understands any conditions of consent, restrictions on use and servicing requirements.

Downloads

Related Insights

Relevant field notes, audit learnings and specification articles.

Tools

Calculators and lookup tools that support this guide.

Applications

Where this regulation topic most commonly appears in real buildings and systems.

Products

Product families commonly specified against this guide.

Quick Links

Downloads

3 documents

Related insights

4 articles

Related tools

1 tool

Applications

3 sectors

Need help specifying?

Our technicians can walk the current risk, the required device, and the assembly that satisfies AIM.

Regulation guide

Insights on

Hose Union Taps

Tools & calculators

Calculate, look up, decide