Regulations 3 and 4; Schedule 2, paragraphs 14, 16, 28, 29 and 31

24 Nov 2026

9

Water Conservation

PropertyValue
Washing machine consumption27 L/kg of washload — standard 60°C cotton cycle
Washer-drier consumption48 L/kg of washload — standard 60°C cotton cycle
Dishwasher consumption4.5 L per place setting
Plug exemption (restricted-flow basin)Maximum 0.06 L/s, subject to Schedule 2 paragraph 28 conditions

The Water Regulations contain requirements intended to prevent the unnecessary consumption and loss of water.

Reducing water consumption also reduces the energy required to treat, distribute and heat water, as well as the costs associated with water supply and wastewater disposal.

Under Regulation 3 of the Water Supply (Water Fittings) Regulations 1999, water fittings must not cause, or be likely to cause, waste, misuse or undue consumption of water.

These requirements apply to the design, installation, use and maintenance of water systems.

Waste, Misuse and Undue Consumption

The Regulations identify three forms of unnecessary water consumption:

  • Waste: Water lost through leaks, faulty fittings or other avoidable losses.
  • Misuse: Water used in an inappropriate or wasteful manner.
  • Undue consumption: Water used in excessive quantities, including where fittings fail to meet applicable consumption requirements.

A washing machine provides a useful example of the differences.

A leaking supply hose causes waste. Using mains water unnecessarily to rotate the drum, without using that water for washing, would be misuse. A machine consuming more water than the applicable requirements allow could constitute undue consumption.

Although the distinction between these terms can depend on the circumstances, the underlying requirement is to prevent unnecessary water consumption.

Regulation 3 also addresses water fittings that are damaged, worn or otherwise faulty.

Importantly for designers, the Regulations refer to fittings that cause or are likely to cause waste, misuse or undue consumption. Compliance must therefore be considered during design, not simply after installation.

Waste

Common causes of water wastage in building services include:

  • Hose union taps left running, damaged or operated without authorisation.
  • Leaking taps and other faulty fittings.
  • Washbasins without suitable plugs or self-closing taps where required.
  • Burst pipes and fittings caused by freezing.
  • Pipework damage from excessive pressure or water hammer.
  • Inadequate expansion capacity in heating or hot-water systems.
  • Leakage caused by corrosion or failed pipe joints.

Water wastage can often be reduced through appropriate product selection, correct installation, pressure control and regular maintenance.

For example, a lockable hose union tap enclosure can help prevent unauthorised use, while an Automatic Waterstop Valve can reduce the consequences of a ruptured appliance supply hose.

Arrow Valves offers the HUTB lockable hose union tap enclosure and AWS20FM Automatic Waterstop Valve for these applications.

Misuse

An example of misuse in building services is using mains water continuously for cooling, allowing it to run to waste instead of circulating it through a suitable cooling system.

System designers should consider whether water can be recirculated or whether an alternative cooling method is more appropriate.

Undue Consumption

Common examples of excessive water consumption include:

  • High flow rates from hand washbasin taps.
  • Excessively long pipe runs causing unnecessary draw-off before hot water reaches an outlet.
  • Excessive water consumption during WC and urinal flushing.

Some of these situations can also constitute waste.

Appropriate pressure control, flow limiting, pipework design and water-efficient fittings can reduce unnecessary consumption.

The Designer’s Responsibility

Consulting engineers have considerable influence over the amount of water a building consumes.

Regulation 4 requires water fittings to be of an appropriate quality and standard, suitable for their intended use and compliant with the applicable requirements of Schedule 2.

Product certification, including WRAS Approval, Kiwa UK Regulation 4 and NSF Reg 4, can provide evidence of conformity.

However, selecting an approved fitting does not automatically make it suitable for every installation.

For example, a tap designed for a low-pressure, gravity-fed system may allow excessive flow if installed on a high-pressure mains or boosted supply.

Designers must consider operating pressure, flow characteristics, materials and the intended application.

Jointing methods and installation quality are also important.

Incorrectly installed compression fittings can fail, particularly on larger pipe sizes, potentially causing significant water loss and property damage.

Alternative methods include soldered capillary joints, press-fit and push-fit connections, provided they are suitable for the installation.

Arrow Valves also offers flat-faced valves and pipe connectors for relevant building services applications.

Reducing Hot Water Dead Legs

Long pipe runs between a hot-water source and an outlet can result in several litres of water being drawn off before hot water reaches the tap.

This water is often wasted while the user waits for the required temperature.

The problem can be reduced through:

  • Insulating hot-water pipework.
  • Installing a suitable hot-water return circuit.
  • Using trace heating where appropriate.
  • Providing local point-of-use water heaters.
  • Positioning hot-water storage vessels close to the outlets they serve.

Reducing dead legs can improve convenience and reduce both water and energy consumption.

Controlling Flow Rates

Water-consuming fittings can be divided into two broad categories.

Flow-dependent consumption

These fittings use water for as long as the outlet remains open. Hand washbasin taps are a common example.

Reducing the flow rate reduces the quantity of water consumed over the same period.

Fixed-volume consumption

These fittings use a defined volume of water during an operating cycle.

For example, filling a washing machine at 0.2 L/s rather than 0.1 L/s does not necessarily change the total water consumed. It simply changes the filling time.

For flow-dependent fittings, consumption can be reduced through two main methods:

  1. Reducing the supply pressure.
  2. Limiting the maximum flow rate.

These approaches perform different functions and can be used together where appropriate.

Pressure Reducing Valves (PRVs)

Pressure Reducing Valves control downstream water pressure and help prevent excessive flow caused by high supply pressure.

A properly selected PRV maintains a controlled downstream pressure across its specified operating range.

A downstream pressure gauge allows the valve setting and operating condition to be checked.

Isolating valves should be provided on either side of the PRV to facilitate maintenance, including cleaning the strainer or replacing the gauge, without draining unnecessary sections of pipework.

Arrow Valves supplies a range of PRVs with optional servicing valves and pressure gauges.

The range includes the PRV536, which can be used where pressure reduction is required to control flow and protect downstream fittings.

Automatic Flow Limiting Valves

Another method of reducing water consumption is to limit the maximum flow rate at individual outlets.

A fixed-orifice restrictor can reduce flow, but its performance depends on the available pressure. Small fixed openings can also be vulnerable to blockage.

An Automatic Flow Limiting Valve (AFL) uses a variable-orifice cartridge to maintain a specified maximum flow across its operating pressure range.

As flow increases towards the selected rate, the cartridge automatically reduces the available opening, restricting further increases in flow.

This allows flow to be controlled without relying solely on pressure reduction.

Arrow Valves AFL Servicing Valves

Arrow Valves’ AFL incorporates a replaceable flow-limiting cartridge within a servicing valve.

The cartridge can be inserted or replaced through a side port without disconnecting the pipework or draining the system.

The range includes eight colour-coded cartridges, allowing the required flow rate to be selected for the application.

The cartridge can also be added after the initial installation where future flow control is required.

The original Arrow tutorial identifies the cartridges as suitable for temperatures up to 60°C and describes their automatic flow-limiting operation at supply pressures up to 10 bar.

The appropriate cartridge should be selected according to the terminal fitting, required flow rate and operating conditions.

Tap Reliability and Water Hammer

Taps with ceramic sealing components are generally less prone to washer deterioration than traditional screw-down taps with rubber washers.

However, their suitability still depends on operating pressure and flow conditions.

Designers should consider:

  • Flow performance on low-pressure, gravity-fed supplies.
  • Excessive flow at higher supply pressures.
  • The potential for water hammer caused by rapid valve closure.
  • Increased operating force, or stiction, under high static pressure.

Flow limiting can help reduce pressure surges associated with rapid changes in flow, but it does not reduce static pressure when no water is flowing.

For this reason, an AFL valve does not perform the same function as a PRV.

In some buildings, a PRV can be used to control the pressure serving several floors, with AFL valves installed at individual outlets to limit consumption.

This approach allows static pressure and flow rate to be controlled separately.

Servicing Valves and Drain Taps

Servicing valves are important for water conservation because they allow fittings to be isolated for repair or maintenance without draining large sections of a water system.

Water Regs UK guidance recommends installing servicing valves as close as practicable to the parts of the system they control.

Providing a servicing valve at each appliance or fitting means a fault can be isolated without unnecessarily interrupting water supplies elsewhere.

Where a group of appliances shares a single isolation valve, maintenance can be more difficult and leaks may continue because isolating the entire group is impractical.

Drain taps are also important.

Suitable drain taps allow sections of pipework to be emptied for maintenance without unnecessarily draining other parts of the installation.

Storage Cistern Connections

Servicing valves should be positioned close to storage cistern connections where appropriate, allowing maintenance to be carried out without unnecessary water loss.

Schedule 2, paragraph 16 contains specific requirements for servicing valves on cistern inlet pipes.

Water Meters and Leak Detection

Water meters provide a practical means of monitoring consumption and identifying potential leaks.

A significant increase in meter readings can indicate unexpected water use.

By isolating sections of the installation and observing the meter, it can be possible to identify where water is being lost.

Meters can also help landlords and building operators monitor consumption across separate parts of a building.

Secondary Metering

Where water consumption needs to be measured for individual tenants or areas, secondary meters can be installed on branches of the distribution system.

Meters used for billing must meet the applicable measurement requirements and provide suitable accuracy across the expected flow range.

Arrow Valves’ BRPMV Branch Valve and Meter Assembly combines several functions within one assembly, including isolation, Double Check Valve protection, pressure reduction and water metering.

Water meters should be provided with suitable isolation for maintenance.

Where required, meters with pulsed outputs can also be connected to a Building Management System (BMS) for consumption monitoring.

Water Consumption Limits for Washing Machines and Dishwashers

Schedule 2, paragraph 29 establishes requirements for water-efficient clothes washing machines, washer-driers and dishwashers.

The Regulations specify consumption thresholds under which the water-efficiency requirement is deemed to be satisfied.

ApplianceWater consumption
Domestic horizontal-axis washing machine27 L/kg of washload for a standard 60°C cotton cycle
Domestic washer-drier48 L/kg of washload for a standard 60°C cotton cycle
Domestic dishwasher4.5 L per place setting

These limits should be considered when specifying appliances.

For more information about backflow protection for these machines, refer to the Clothes Washing & Dishwashing Regulation Guide.

Plugs and Self-Closing Taps

Schedule 2, paragraph 28 requires baths, washbasins, sinks and similar appliances to incorporate a watertight, readily accessible plug or another device capable of closing the waste outlet, subject to specified exemptions.

The purpose is to avoid unnecessary water consumption by allowing water to be retained rather than continuously running to waste.

The requirement does not apply to certain appliances, including:

  1. Appliances supplied exclusively through spray taps.
  2. Washbasins or washing troughs that cannot accept a plug and are supplied at no more than 0.06 L/s through a fitting designed for that purpose.
  3. Washbasins or washing troughs fitted with self-closing taps.
  4. Shower baths or shower trays.
  5. Drinking water fountains or similar facilities.
  6. Appliances designed for use with an unplugged outlet in medical, dental or veterinary premises.

Self-closing taps are therefore particularly useful in public washrooms and other locations where taps could otherwise be left running.

The Arrow Valves SPWPSC Standpipe is an example of a standpipe incorporating a self-closing non-hose tap and bucket shelf.

Hose Union Taps and Water Conservation

Hoses used for garden watering and other applications should incorporate a handheld control device, such as a self-closing trigger.

This allows the user to stop the water flow without returning to the tap, helping prevent unnecessary consumption.

A self-closing trigger is not a recognised form of backflow protection.

Suitable backflow protection must still be provided according to the Fluid Category risk and intended use of the hose connection.

Where unauthorised use is a concern, lockable hose union tap enclosures and standpipes can provide additional protection against water wastage.

Swimming Pools and Ponds

Swimming pools supplied with mains water should be covered when not in use where practical, reducing water loss through evaporation.

Pools should also be inspected for leaks.

Schedule 2, paragraph 31 requires ponds, fountains and pools to have an impervious lining or membrane to prevent water leakage or seepage.

These requirements are intended to reduce unnecessary water loss from stored water features.

Rainwater and Greywater Systems

Rainwater harvesting and greywater recycling can reduce demand on the wholesome water supply by providing water for suitable non-drinking applications.

The Water Regulations do not generally require buildings to incorporate these systems, but they establish requirements for preventing contamination where alternative water supplies are used.

Rainwater and greywater systems are normally considered Fluid Category 5 contamination risks.

They must be adequately separated from the wholesome water supply, and the pipework must be clearly identified to prevent cross-connections.

Schedule 2, paragraph 14 addresses connections to systems containing water that is not wholesome.

For suitable installations, Arrow Valves offers the AB18T Rainwater Header Break Tank, incorporating a Type AB air gap.

Summary

When designing water systems to minimise waste, misuse and undue consumption:

  1. Reduce excessive supply pressures using suitable PRVs.
  2. Limit flow rates at points of use where appropriate.
  3. Specify water-efficient fittings and appliances.
  4. Protect hose union taps against unauthorised use.
  5. Minimise unnecessary hot-water dead legs.
  6. Provide suitable servicing valves and drain taps for maintenance.
  7. Use water meters to monitor consumption and identify leaks.
  8. Ensure water fittings are suitable for their operating conditions and intended use.

Downloads

Related Insights

Relevant field notes, audit learnings and specification articles.

Tools

Calculators and lookup tools that support this guide.

Applications

Where this regulation topic most commonly appears in real buildings and systems.

Products

Product families commonly specified against this guide.

Quick Links

Downloads

3 documents